For an existing antifreeze system without a backflow prevention device, what size hole is required in the check valve separating the supply and the antifreeze?
If sprinklers are above the level of the water supply to the antifreeze system, a check valve with a 1/32 in. (0.8 mm) hole in the clapper shall be provided in the U-loop.
What standard applies for underground malleable iron threaded fittings of Class 150?
ASME B16.3 is the standard that applies to malleable iron threaded fittings of Class 150, which are commonly used in piping systems, including those for fire protection. This standard covers dimensions, tolerances, and material requirements for these types of fittings.
Annual testing for a 1,500 gpm (5,677 L/min) at 80 psi (1.4 bar) fire pump supporting an attached sprinkler system
demand of 1,800 gpm (6,813 L/min) at 100 psi (6.9 bar) is being conducted. The flow test of the fire pump must
achieve what minimum flow rate and discharge pressure?
For annual testing of fire pumps, NFPA standards require the pump to be tested at its rated capacity and pressure, as well as at 150% of its rated capacity at a correspondingly lower pressure. In this scenario, the minimum flow rate required for the test is the demand of the attached sprinkler system, which is 1,800 gpm at 100 psi, to ensure the pump can meet or exceed the system's highest demand.
The purpose of the owner's certificate is to
The owner's certificate is a form that the owner or the owner's representative fills out to provide information about the property, the intended use of the building, the existing or planned construction, and the presence of any special materials, occupancies, or hazards. The purpose of the owner's certificate is to help ensure that the capability of the sprinkler system is adequate to address the hazard and that the design and installation of the fire sprinkler system are based on accurate and complete information. The owner's certificate is not intended to replace project plans, obtain the building permit, or be a declaration by the sprinkler contractor as to the hazards in the building.
What is the minimum temperature rating of ceiling sprinklers in roll paper stored at 15 ft. (4.6 m) or less?
The minimum temperature rating for ceiling sprinklers in roll paper storage areas that are 15 ft or less in height is typically 150F (66C). This rating is selected to provide a buffer between the ambient temperature conditions and the activation temperature of the sprinklers, preventing accidental activation.
Marsha
7 days agoChau
15 days agoTheron
22 days agoCandra
1 month agoAdelina
1 month agoAlbina
2 months agoKenny
2 months agoBrynn
2 months agoParis
2 months agoGladys
3 months agoGeraldine
3 months agoYesenia
3 months agoTrevor
3 months agoLouann
4 months agoJaney
4 months agoWhitley
4 months agoChara
4 months agoEvangelina
5 months agoMargurite
5 months agoSanjuana
5 months agoRhea
5 months agoIrma
6 months agoCharlesetta
6 months agoMertie
6 months agoEmerson
6 months agoTawna
7 months agoCarolann
7 months agoFranchesca
9 months agoRosendo
10 months agoCharisse
11 months agoCherelle
12 months agoPaulina
1 year agoKate
1 year agoNichelle
1 year agoGabriele
1 year agoOlen
1 year agoDetra
1 year agoJoye
1 year agoBernardine
1 year agoCharlette
1 year agoBarrett
1 year agoMicah
1 year ago